PA4400A Three Phase AC Power Analyzer with optional 4th channel
PA4400A 3 Phase Power Analyzer from Lexcom
The PA4400A series offers single phase, two wattmeter and three phase power analysis, with full power meter and watt meter capability. Three phase power analyzers / watt meters are a necessity when several ac power measurements need to be recorded during testing – from one set of input connections. Three phase watt meters are important when accurate watts measurement is necessary for certification and traceability. In addition to power measurement (watts), energy, reactive power (VAr), apparent power (VA), voltage rms, current rms, power factor and harmonics, can all be viewed with ease. All Lexcom power meters / wattmeters simply connect between the ac supply and the load, various current transformer and shunt options allow measurement with any level of current amplitude. Typical three phase watt meter applications include appliance testing like generators, electric stoves, heating, air conditioning, pumps, fans, electronic lighting and motor controllers. All our power meters are equipped with safety terminals (4mm/banana) along with optional “breakout” boxes and clamp probes for fast and safe measurement.
|
|
Multiple Parameter Display View results on all four channels plus neutral and Sum. Choose between individual channels or all results on one page. Scaling factors may be applied to give correct readouts when using VT and CT. One key access to most display functions. |
|
Waveforms + Chart Recorder Functions View volts, amps and watts waveforms for each channel. Use datacapture to store and analyse transient events. A chart recorder function graphs a selected parameter over time. |
|
Harmonic Analysis Harmonic analyser allows user to view harmonic lists or bar graphs for all four channels. Amps and volts THD is calculated from the harmonic series |
Measurement Function |
PA4400A |
|
Measurement Bandwidth | Range | DC, 0.2Hz to 500kHz |
Volts | Display Resolution | 4 3/4 digit |
Measurement Range | 700mVrms to 1000Vrms (1440Vpk) | |
(200mVrms with display blanking off) | ||
Vpeak Ranges | 1440, 720, 220, 110, 33.0, 16.0, 5.0, 2.5 | |
Max input volts | 1440Vpk Overload 3000Vrms for 1 second | |
Accuracy | 0.1% Reading +0.1% Range +10mV DC 0.5% Reading +0.5% Range +10mV |
|
Common mode | 90dB | |
Input impedance | 1Mohm 12pF | |
Current | Display Resolution | 4 3/4 digit |
Measurement Range | 0.01Arms to 20Arms (125Apk) | |
Ext Shunt 1mVpk to 4Vpk | ||
Apeak Ranges | 125, 62.5, 22.0, 11.0, 3.50, 1.80, 0.6, 0.3 | |
Max input amps | 20Arms continuous 125Apk | |
Accuracy | 0.1% Reading +0.1% range +2mA | |
DC 0.5% Reading +0.5% Range +10mA | ||
Common mode | 90dB | |
Input impedance | 0.02Ohm | |
Power | Accuracy | 0.1% Reading +0.1% range +2mW |
VA | Accuracy | 0.1% Reading +0.1% range +2mVA |
VAR | Accuracy | 0.1% Reading +0.1% range +2mVAR |
General Specifications |
||
Interfaces | Standard | Printer (Centronics) |
Optional | IEEE-488, RS232, Chart Recorder x 10 | |
Environment | Operating Temperature | 0°C to +50°C |
Storage Temperature | -40°C to +60°C | |
Humidity | 10% to 90% RH non-condensing | |
Dielectric Strength | Inputs to case | 4kV AC 50/60Hz for 1 minute |
AC line input to case | 2kV AC 50/60Hz for 1 minute | |
Power | AC line input voltage | 90V to 264V |
AC line input frequency | 45Hz to 450Hz | |
AC line input fuse | 20mm 1AT | |
Power consumption | 25W/40VA | |
Mechanical | Weight | 9.0kg |
Dimensions (W x H x D) | 430mm x 144mm x 420mm |
Options and description |
|
PA4400A-3 | Three Phase Power Analyser – 3 Channel |
PA4400A-4 | Three Phase Power Analyser – 4 Channel |
PA4400A-3-B | With Blank Front Panel |
PA4400A-4-B | With Blank Front Panel |
Option 68 | Interface Board (use with Option 68A, 68B, 68C) |
Option 68A | RS232 |
Option 68B | IEEE-488 |
Option 03 | 500A PA Series Current Transducer 100:1 |
Option 04 | 1000A PA Series Current Transducer 1000:1 |
Option 22 | PA4400A Rack Mounting Kit |
Option 25 | HV 40kVpk 2000:1 Probe |
Option 29 | PA4400A-3 Test Lead Set |
Option 29A | PA4400A-4 Test Lead Set |
Option 43 | PA4400A-3 UKAS Certificate |
Option 44 | 3000A Clamp Current Transformer |
Option 46 | PA Series 1mA to 500mA non inductive shunt |
Option 49 | 1250A/125A:1A (1500A max) 0.2% CT |
Option 50 | PA4400A-4 Torque/RPM Input |
Option 51 | Hall Effect sensor 50A Current CT |
Option 52 | Hall Effect sensor 100A Current CT |
Option 53 | Hall Effect sensor 200A Current CT |
Option 54 | Hall Effect sensor 300A Current CT |
Option 55 | Hall Effect sensor 500A Current CT |
Option 56 | Hall Effect sensor 1000A Current CT |
Option 57 | Wiring/Housing for LEM’s (PSU not inc.) |
Option 58A | 1A PSU for Hall Effect Transducers (cased) |
Option 63 | AVLab 44 for PC |